Plan Code Room # Comments
     
A2-1.3 1213 1. Move custodial sink to North wall next to overhead door.
M1-1.3 1213 1. Compressed air lines? - Can't find.
A2-1.3 1213A 1. Wood block flooring in this area.
M2-1.3 1213B 1. Ventilation provided for welding room adequate for fume removal?
A2-1.3 1200 1. Custodial sink on West wall just North of mezzanine. 2. Is the slab under the high bay rated at 20 tons -- couldn't find spec.
A2-1.3 1200D 1. Custodial sink on West wall. North of door.
AQ1-1.3 1200D 1. Paint spray booth not shown. 2. Fume hood not shown.
M1-1.3 1200 1. Floor drain not shown. 2. Compressed air lines? - Can't find.
M2-1.3 1200 1. HVAC ducting covers only 1/2 of room?
A2-4.1 4254 1. Room needs a door.
A2-4.1 4278 1. Can North door be relocated to the East side of the conference room?
E4-1.1 1410B 1. Add same cart connections in lecture rooms to this room.
A2-0.1 B102 1. Floor of B102 must be level with floor of ramp of Chemistry at his point. Need to wheel heavy dewars in and out of B102. 2. Place 1ft by 1ft square hole in wall between B102 and B104, 10ft above floor near center of wall.
E4-0.1 B102 1. Need wall phone.
E4-0.1 B104 1. Need wall phone. 2. Need 2 data lines.
A2-0.1 B104 1. Place 1-ft by 1-ft square hole in wall between B102 and B104: 10ft above floor, near center of wall.
A2-0.1 B104 1. Holes in floor of B104--three sets consisting of five 6" ID holes in a straight line with 1ft. separation of centers. Center of holes should be parallel to adjacent wall (specified below) and 6" from wall. Set 1: East wall, in South half of room. Set 2: West wall, in North half of room. Set 3: Centered along North wall.
E2-0.1 B104 1. 480-V service unclear: Correct amperages are marked in correct locations, but cannot tell if this service is really 480-V. 2. Need 208V-20A, single phase power to sub-basement. Install start-stop switch in West wall next to the 480V switches.
A2-0.2 B149 1. Add 6' by 15 1/2' interior room as shown with T-1 wall and same dropped ceiling. Are there separate slab and air handling isolation in specs.? Any plumbing in this area? (see attached picture)
E2-0.1 B108 1. 480-V service unclear: Correct amperages are marked in correct locations, but cannot tell if this service is really 480-V.
E2-0.1 B130 1. 480-V service unclear: Correct amperages are marked in correct locations, but cannot tell if this service is really 480-V.
M1-0.1 B136A 1. Plumbing - there is none in the drawing! Should be 4 cold water supplies, 2 cup drains, 4 accesses to circulated chilled water & 2 floor-drains. 2. In fact, where is the chilled water supply? I don't see it at all.
E2-0.1 B136 1. Add 1 250V 30 - 30A twist lock recepticle on south wall.
A2-0.1 B136 1. "Openings" should be windows in leaded glass.
E4-0.1 B135 1. Wall phone socket on south wall near data sockets.
A2-0.1 B135 1. "Openings" should be windows of leaded glass.
A2-0.1 B133 1. Add fume hood in this room, on south wall.
E3-4.2 4210 1. Should be 3 tube fixtures - at least-assuming 40 watt tubes - or 35-37 watt "MISU" tubes. Switched inner & outer with 2 switches so that lighting is: (1) all off; (2) center on 1 tube; (3) outer two tubes; (4) all 3 tubes on.
E3-4.2 4208B 1. Should be 3 tube fixtures - at least-assuming 40 watt tubes - or 35-37 watt "MISU" tubes. Switched inner & outer with 2 switches so that lighting is: (1) all off; (2) center on 1 tube; (3) outer two tubes; (4) all 3 tubes on.
E3-4.2 4208D 1. Should be 3 tube fixtures - at least-assuming 40 watt tubes - or 35-37 watt "MISU" tubes. Switched inner & outer with 2 switches so that lighting is: (1) all off; (2) center on 1 tube; (3) outer two tubes; (4) all 3 tubes on.
E4-4.2 4210 1. Needs to become an "office" remove wall phone & fire alarm, add telephone and data per specs for an office.
E2-4.2 4210 1. Can't tell how much actual power is available - each office should have the sole use of a 20 amp circuit - at least.
E2-4.2 4208B 1. Can't tell how much actual power is available - each office should have the sole use of a 20 amp circuit - at least.
E2-4.2 4208D 1. Can't tell how much actual power is available - each office should have the sole use of a 20 amp circuit - at least.
A2-4.2 4208B 1. Does not have a sound rated partition.
A2-1.1 1116 1. No wall type on west wall.
E2-1.1 1116 1. Should probably have a smoke detector.
E4-3.2 4214A 1. Should have 1 phone - wall and 1 data in mail room. Also a second the fixutre - turn other direction or make the one a 4 tube ?.
A2-4.2 4210-1 1. Change door types to N2, F, etc. to match offices.
A2-4.2 4211-2 1. Change door types to N2, F, etc. to match offices.
A2-3.2 3214A 1. Wall type not shown. Suggest E for all 3/4 sides.
A2-3.2 3208 1. Change door to south-east corner of room. (back of conference room)
E2-1.3 1221 1. Emergency power in one electrical circuit on east wall. 2. Emergency power in communications rooms serving 1221 (e.g. 1119, 1232, B119)
A2.0.1 B114 1. Location of floor access holes not shown. (See attached sheet.)
AQ1-0.1 B114 1. Location of sink on East wall should be reversed -- on B112 side.
M1-0.1 B114 1. No indication of plumbing connections and drains.
E2-0.1 B114 1. 125V, 30A conduit to shielded room from E wall (not shown). 15' bench height power strip not shown on electrical - (see lighting?) - does this have 125V power as requested, plus 1 250V recepticle?
E2-0.1 B108A 1. Electrical disconnects not shown.
M1-0.1 B108A 2. Plumbing: water and drains not shown.
M2-0.1 B108A 1. HVAC: HEPA filters in vinyl ceiling (cleanroom type). Air return via hanging flexible ("soft wall") sides. Hung from metal frame on 2 sides of lab (E,W). Air flow controlled by fan controls i.e. variable speed HEPA modules (50% coverage).
M1-0.1 B238 1. Eye wash station - drains in the floor?
A2-3.2 3214A 1. Can we have built in mail boxes?
A2-1.3 1266A 1. Add 125V power to all walls. 1 duplex on N, 2 on E, 1 on S, 2 on W.
AQ1-0.1 B175 1. Add fume hood on North wall in NW corner.
A2-0.1 B131 1. Can there be a vibration isolation joint in the floor along the line defined by the sub-basement end wall?
A2-7.2 7170 1. Is it possible to have an access door to the telescope storage room from inside the penthouse?
A2-7.2 ROOF 1. Are the small circles telescope pillars?
A2-7.2 ROOF 1. 110V power is need on the observation platform. The telescope pillars are a good location. 2. Any roof lighting should be dimmable.
A2-1.3 1219A 1. Move the roof port as close to the outside wall as possible.
E2-1.3 1230 1. Add R2 raceway around entire wall.
E2-4.1 4270 1. Add duplex 110V outlets: 2 on W, 2 on N and 2 on S.
A2-0.1 B111 1. Add remaining floor holes as shown in drawing.